  • Alarm Input wiring can be sensitive to electromagnetic interference so it is recommended to use a high quality shielded cable.

  • Strip only enough of the cable jacket and shielding to allow for proper wiring of the connector.

  • The shield foil/braid should be stripped to the same length as the cable jacket.

  • The shield wire should be stripped to the same length as the signal conductors.

  • The shield wire should be terminated at the controller using the dedicated shield connection of the supervised alarm connector. The other end of the cable shield should be left unconnected.

  • Ensure exposed shield wire does not come into contact with any other shield wires, the metal enclosure, or any other metallic surfaces. 

  • Shrink tubing can be used on exposed shield wire to ensure unwanted contact with metal surfaces.

  • Shrink tubing can be used on exposed shield wire to ensure unwanted contact with metal surfaces.

Relay Wiring

...

Example of Relay Wiring

...